FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
0001
-3
0004
-1
0005
-1
0006
-1
Issue 01 (2019-03-05)
Alarm
Sever
System Action
Name
ity
Mains
Minor
If there is no
Ph.
battery, the system
reverse
transfers to bypass
d
mode or shuts
down based on
logic.
Mains
Minor
If there is no
neutral
battery, the system
absent
transfers to bypass
mode or shuts
down based on
logic.
Mains
Minor
If the rectifier is
underv
overloaded due to
oltage
rectifier derating,
the system switches
to batteries or D.G.
or shuts down
based on logic.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
The mains is
Check the mains
abnormal.
power.
Cable connections
Verify the cable
are incorrect.
connections.
1. Secure or
Cable connections
are incorrect.
2. Check that the
The mains is
Check whether the
abnormal.
mains voltage
ranges from 80 V
The power
(excluding 80 V) to
module
176 V. If no, the
sampling
mains monitoring
circuit is
circuit for the power
abnormal.
module is faulty.
Replace the faulty
3 Alarm Reference
voltage is less
than 80 V, the
mains voltage is
abnormal; if the
mains voltage
exceeds 88 V,
the power
module
sampling circuit
or fuse may be
abnormal.
Replace the
faulty module.
connect the
neutral wire to
the cabinet if it
is loose or
disconnected.
neutral wire to
the power
distribution
system is
normal.
56