Huawei FusionModule5000 Maintenance Manual page 60

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Alarm
Name
Main input
breaker
tripping
Main input
overvoltage
Main input
undervoltag
e
Main input
overfrequen
cy
Main input
underfreque
ncy
Main input
overload
Max. main
input cur.
exceed
Issue 01 (2019-03-05)
Alarm
Impact
Severity
Critical
The mains switch
has tripped.
Critical
Input
overvoltage:
Input voltage V >
1.2 x Rated
voltage (Multiple:
1.05–1.25;
confirmation
time: 2–10s).
Critical
Input
undervoltage:
Input voltage V <
0.85 x Rated
voltage (Multiple:
0.75–0.95;
confirmation
time: 2–10s).
Major
The input
frequency is 1.5
Hz higher than
the configured
frequency. The
frequency setting
range is 50–60
Hz.
Major
The input
frequency is 1.5
Hz lower than the
configured
frequency. The
frequency setting
range is 50–60
Hz.
Critical
A phase input
current of a route
exceeds 1 time of
the rated current
(multiple: 1–1.2;
confirmation
time: 1–10s).
Warning
A phase input
current of a route
exceeds 0.8 time
of the rated
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm Reference
Possible
Solutions
Cause
The back-end
Check whether the
is
back-end current is
short-circuited
short-circuited or
or experiences
experiences
overcurrent.
overcurrent.
The input
Check the input power.
power supply
is faulty.
The input
Check the input power.
power supply
is faulty.
The input
Check the input power.
power supply
is faulty.
The input
Check the input power.
power supply
is faulty.
The system is
Check all output load
overloaded.
power.
The system is
Check all output load
overloaded.
power.
52