A water sensor consists of a water detection rope, water detector, and conversion cable. The
water detection cable is laid out on the floor, connected to the water detector placed near the
collector by the conversion cable.
Figure 5-73 Water sensor components
(1) Water detector
(4) Conversion cable end B,
connecting to water the
detection rope
Recommended tools and materials: crimping tool
Procedure
Step 1 Replace the water detector.
1.
2.
3.
Issue 01 (2019-03-05)
Remove the conversion cable at the conversion port for the water detector and
conversion cable.
Connect a new water detector to the conversion cable, as shown in
Secure the new water detector.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure 5-73
shows the components.
(2) Conversion cable end A,
connecting to the water detector
(5) Water detection rope end A,
connecting to the conversion
cable
5 Parts Replacement
(3) Conversion cable
(6) Water detection
rope
Figure
5-74.