FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Maintenance
Item
Check the
availability of
the access
actuator.
Issue 01 (2019-03-05)
Maintenance
Operation
Period
Semi-annually
On the WebUI
of the ECC800,
choose
Monitoring >
Aisle > Access
Actuator
Group >
Access
Actuator to
enter the
Controls page,
and remotely
control the
doors.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2 Routine Maintenance
Standard
Troubleshooti
ng
abnormal. If
gateway is
the RUN
not
indicator
energized. If
blinks
so,
slowly, the
reconnect
access
the cable. If
actuator is
not, replace
running
the access
normally. If
actuator.
the RUN
If the RUN
indicator
indicator
blinks at
blinks at
short
short
intervals, the
intervals,
communicat
check
ion is
whether the
interrupted.
communicat
The ALM
ions cable is
indicator is
properly
off.
connected.
If not,
reconnect
the cable. If
so, replace
the cable.
If the ALM
indicator is
steady on,
clear the
alarm by
referring to
ECC800
Alarm
Reference
V100R001.
The smart
If the smart
module aisle
module aisle
doors can be
doors cannot be
normally
normally
controlled
controlled,
through the
check whether
access actuator.
the magnetic
lock cable is
loose or
disconnected. If
so, reconnect
the cable. If not,
replace the
access actuator
or magnetic
41