FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Alarm ID
0x5011
0x5012
0x5013
0x5014
0x5015
0x5016
0x5017
Issue 01 (2019-03-05)
Alarm
Alarm
Name
severity
POE2 output
Major
overload
POE3 output
Major
overload
POE4 output
Major
overload
Detection
Critical
board
abnormal
L1
Critical
open-phase
L2
Critical
open-phase
L3
Critical
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Solution
Cause
is overloaded
not overloaded.
or the power
2. Check that the power
supply pin of
supply pin of the first
the first branch
branch is not
is
short-circuited.
short-circuited.
1. Check that the output
The output of
of the second branch
the second
is not overloaded.
branch is
overloaded or
2. Check that the power
the power
supply pin of the
supply pin of
second branch is not
the second
short-circuited.
branch is
short-circuited.
1. Check that the output
The output of
of the third branch is
the third
not overloaded.
branch is
overloaded or
2. Check that the power
the power
supply pin of the
supply pin of
third branch is not
the third
short-circuited.
branch is
short-circuited.
1. Check that the output
The output of
of the fourth branch
the fourth
is not overloaded.
branch is
overloaded or
2. Check that the power
the power
supply pin of the
supply pin of
fourth branch is not
the fourth
short-circuited.
branch is
short-circuited.
The monitoring
Check that the
board is faulty.
monitoring board works
properly.
The L1 phase
Check the power input.
voltage is
below the
open-phase
threshold.
The L2 phase
Check the power input.
voltage is
below the
open-phase
threshold.
The L3 phase
Check the power input.
3 Alarm Reference