Huawei FusionModule5000 Maintenance Manual page 32

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
No.
10
11
12
Issue 01 (2019-03-05)
Operation
are working
properly. Five
seconds later two
condensate pump
would start. Put
down the two floats.
Do not hold the two
floats up so long, to
avoid pumping air for a
long time.
Start the indoor unit,
choose Maint >
Diagnostic Mode >
Enter from the main
screen, and set
Humidifier to 50%.
Check whether water
can be injected
smoothly.
(Following the
preceding step) Set
Humidifier to 0%, and
press the manual water
drain button on the side
of the electric control
box to "OFF" to check
whether water drainage
is normal. After the
check is complete, set
the manual drainage
button on the side of the
electric control box to
"ON".
NOTE
Ensure that the manual
drainage button on the
side of the electric control
box is set to "ON" after
the check ends.
Otherwise, the humidifier
will not be filled with
water when it is running.
Start the indoor unit,
choose Maint >
Diagnostic Mode >
Enter from the main
screen, and set electric
heater to On. Check that
the electric heater
generates heat.
NOTE
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting
Check that the water inlet
sluice is open.
Disconnect the humidifier
water injection hose and clear
the blockage in the hose.
Disconnect the drainpipe from
the device, and use a rubber
mallet to knock the drainpipe to
remove foreign matter or
impurities from the drainpipe.
Then remove the water pump
and clean up impurities from the
water pump. If the impurities are
too much to be cleared, replace
the water pump.
NOTE
When installing a pipe, seal
screw thread joints using water
sealant and ensure that no water
leaks.
If the fault persists after the
maintenance, see section
Troubleshooting the Cooling
System
for further processing.
Replace the electric heater by
referring to
5.2.6 Replacing an
Electric
Heater.
2 Routine Maintenance
Period
Result
□Passed.
Quarterl
y
□Failed.
□Passed.
Quarterl
y
□Failed.
4.2
□Passed.
Quarterl
y
□Failed.
24