Procedure
Step 1 Open the rear door and remove the air filter.
Step 2 Switch the manual drain button on the side of the electric control box to the ON position to
drain water in the humidifier cylinder.
Step 3 Tap Shutdown on the main screen and power off the device. Then switch the button back to
OFF.
Step 4 Unfasten the screws on the evaporator hose clamp to loosen the evaporator hose, as shown by
(1) in
Figure 5-36 Removing the humidifier cylinder
Step 5 Cut off the cable ties, as shown by (2) in
Step 6 Remove the belt clamp on the humidifier cylinder, as shown by (3) in
Step 7 Pull upward to remove the humidifier cylinder, as shown by (4) in