FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
0010
-1
0010
-2
0011
-1
0012
-1
Issue 01 (2019-03-05)
Alarm
Sever
System Action
Name
ity
1. The system
Abnor
Minor
cannot transfer
mal
to bypass mode.
bypass
voltage
2. The system
transfers to a
working mode
based on the
current power
supply status
and logic.
1. The system
Bypass
Minor
cannot transfer
ph.
to bypass mode.
reverse
d
2. The system
transfers to a
working mode
based on the
current power
supply status
and logic.
1. The system
Bypass
Minor
cannot transfer
neutral
to bypass mode.
absent
2. The system
transfers to a
working mode
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
module.
1. Check the
The bypass
voltage range
is not correctly
set.
The bypass
2. Check the
input voltage
is abnormal.
1. Check the
The bypass
frequency
range is not
correctly set.
The bypass
2. Check the
input
frequency is
abnormal.
The phase
Check whether the
sequence of the
cable phase
three-phase
sequence is correct
bypass input is
based on the phase
reversed.
sequence table. If
no phase sequence
table is available,
exchange the
positions of any two
cables.
1. Secure or
The neutral wire
of bypass input is
absent.
3 Alarm Reference
bypass input
voltage or cable
connections with
a multimeter.
voltage system
and bypass
voltage
thresholds
configured on
the LCD.
bypass input
voltage or cable
connections with
a multimeter.
bypass input
frequency.
Check the rated
frequency and
frequency range
configured on
the LCD.
connect the
neutral wire to
the cabinet if it
is loose or
disconnected.
57