Huawei FusionModule5000 Maintenance Manual page 20

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Powering off the PDC may interrupt all services. Before disconnecting power, ensure that
related emergency plans have been worked out and permissions have obtained from parties
involved. Huawei bears no responsibility for any accidents or loss.
Table 2-6 Routine maintenance for the PDC
Maintenance
Item
Three phase
power
indicators
Surge
protection
module
Liquid crystal
display (LCD)
screen on the
PDC
Connections of
input power
cables and
output power
cables
Signs of rodent
movements in
Issue 01 (2019-03-05)
Maint
Operation
enanc
Guide
e
Interv
al
Monthl
Check the
y
luminance of
the indicators.
Monthl
Check the
y
status of the
surge
protection
module
indicator and
circuit breaker.
Monthl
Touch the LCD
y
screen with
your finger.
Monthl
Visual
y
observation
Monthl
Visual
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2 Routine Maintenance
Expected
Exception Handling
Result
The three
Replace the indicator that
phase power
generates no or dim light by
indicators
referring to
are steady
Replacing an
on.
The surge
If the indicator of an
protectio
SPD module is red,
n module
replace the SPD module
indicator
by referring to
is green.
Replacing an SPD
Module.
The
circuit
If the circuit breaker is
breaker is
switched off, switch it
switched
on.
on.
The LCD
Check whether the power
screen panel
cable is properly connected,
is in good
and replace the LCD screen
condition.
if necessary by referring to
5.1.1.6 Replacing an
The
Take measures depending
cables are
on the severity.
not
damaged.
The
terminals
are intact
and
secure
and free
from
spark
signs and
rust.
There is no
If there is a sign of rodent
sign of
movements, ask a
5.1.1.2
Indicator.
5.1.1.1
MDU.
12