Huawei FusionModule5000 Maintenance Manual page 151

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Procedure
Step 1 Open the rear door.
Step 2 Remove the air filters.
Step 3 Push up the buckle button on the rack, as shown by (1) in
If the rectifier is blocked by cable X101 or X102, you can remove terminal X101 or X102 and
then reconnect it after the replacement is complete.
Figure 5-40 Replacing the rectifier
Step 4 Pull out the buckle, as shown by (2) in
from the plug-in frame.
Issue 01 (2019-03-05)
The figure is for NetCol5000-C030H6B2010020E1 only.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure
Figure
5-40, and then pull out the rectifier module
5 Parts Replacement
5-40.
143