Huawei FusionModule5000 Maintenance Manual page 80

Smart modular data center
Hide thumbs Also See for FusionModule5000:
Table of Contents

Advertisement

FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Alarm ID
0x5013
0x5014
0x5024
0x5025
0x5026
0x5027
0x5028
0x5029
Issue 01 (2019-03-05)
Alarm Name
Alarm
severity
Fourth output
Major
overloaded
Detection board
Critical
abnormal
Branch 1
Critical
overloaded
Branch 2
Critical
overloaded
Branch 3
Critical
overloaded
Branch 4
Critical
overloaded
Branch 5
Critical
overloaded
Branch 6
Critical
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 Alarm Reference
Possible
Solution
Cause
is
supply pin
short-circuited.
of the third
branch is not
short-circuit
ed.
1. Check that
The output of
the fourth
the fourth
output is not
branch is
overloaded.
overloaded or
the power
2. Check that
supply pin of
the power
the fourth
supply pin
branch is
of the fourth
short-circuited.
branch is not
short-circuit
ed.
The detection
Check that the
board hardware
monitoring
is faulty.
board works
properly.
The current of
Check the
the first output
power of the
branch exceeds
load on the
the threshold.
corresponding
branch.
The current of
Check the
the second
power of the
output branch
load on the
exceeds the
corresponding
threshold.
branch.
The current of
Check the
the third output
power of the
branch exceeds
load on the
the threshold.
corresponding
branch.
The current of
Check the
the fourth
power of the
output branch
load on the
exceeds the
corresponding
threshold.
branch.
The current of
Check the
the fifth output
power of the
branch exceeds
load on the
the threshold.
corresponding
branch.
The current of
Check the
the sixth output
power of the
72