FusionModule5000 Smart Modular Data Center
Maintenance Guide (ECC800)
Alar
m
ID
(Ala
rm
ID-
Cau
se
ID)
0025
-1
0026
-1
Issue 01 (2019-03-05)
Alarm
Sever
System Action
Name
ity
1. The current
Battery
Minor
limit value is
overvol
derated when
tage
the battery
voltage exceeds
the overvoltage
alarm threshold.
2. The system
disconnects the
charge loop
when the
battery voltage
is higher than
the overvoltage
protection
threshold
(overvoltage
alarm threshold
+ 0.05 V/cell).
Low
Minor
The system triggers
battery
dry contact outputs.
voltage
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Cause
Solution
1. Check whether
The
configured
number of
batteries is
less than the
2. If they are
actual number.
The battery
neutral wire is
3. Check whether
absent.
1. If the low
Battery
discharge
results in low
battery
voltage.
The battery
neutral wire is
absent.
The charger is
faulty.
2. Check whether
3. If this alarm is
3 Alarm Reference
battery
parameters are
correctly set.
correctly set,
certain batteries
may be faulty.
the battery
neutral wire is
correctly
connected.
battery voltage
alarm is
generated in
battery mode,
check whether
the mains
voltage recovers.
If yes, charge
batteries
immediately.
the battery
neutral wire is
correctly
connected.
generated in
normal mode,
check whether
the battery
switch is ON. If
yes, the charger
may be faulty.
Replace the
59