Electric Metering - Combined Kw Of Monitored Equipment - Carrier OPN-OPT-OL Installation And Startup Manual

Chilled water system optimizer v2
Table of Contents

Advertisement

Point Name/Description
Low CWS Temp. Setpoint limit at Low Load = CHWS Setpoint + __ degrees
Low CWS Temp. Setpoint limit at High Load = CHWS Setpoint + __ degrees
Method 3 — This is a simple low limit.
Allow condenser water temperature setpoint to drop no lower than: __ degrees
Current Limits, Approach, Setpoints, and CWS Temperature Setpoint
Current High Limit is: — Displays value.
Current High Approach is: — Displays value.
Current Setpoint is: — Displays value.
Current Low Approach is: — Displays value.
Current Low Limit is: — Displays value.

Electric Metering - Combined kW of Monitored Equipment

Navigation:
i-Vu®
Point Name/Description
Meter Input
Instantaneous Demand: __ kW — Displays value of the instantaneous demand read by
meters.
Alarm:
IN FAIL — Displays the status of the meter input based on the criteria selected below
Send Alarm if meter input < x with hysteresis of y for greater than _:__ mm:ss
Where:
x = alarm threshold in Kw
y = hysteresis amount
_:__ mm:ss = delay time in minutes and seconds
Reset History
Reset ALL values to zero? — Provides the ability to reset all meter data and history
Chilled Water System Optimizer v2
Installation and Start-up Guide
Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Properties
Control Program
>
Electric Metering - Combined kW of Monitored Equipment
89
Range
D:
10°F
R:
10 to 30°F
D:
30°F
R:
20 to 40°F
D:
55°F
R:
53 to 75°F
>
Range
D:
30:00 mm:ss
R:
10:00 to 60:00 mm:ss
D:
No
R:
No/Yes
CARRIER CORPORATION ©2019
All rights reserved