Wiring For Communications; Ethernet Wiring Specifications - Carrier OPN-OPT-OL Installation And Startup Manual

Chilled water system optimizer v2
Table of Contents

Advertisement

Wiring for communications

The controller has multiple ports. See table below for port descriptions.
Port
Protocol
Ethernet
BACnet/IP
Port E1
Modbus/IP
NOTE Both
protocols can
run
simultaneously
S2*
Modbus
Local
Enhanced
Access
Access
* The Config Mode DIP switch Console must be Off (down position) to use Port S2. Port S2 supports only one
protocol and one wire type at a time.
CAUTION The Chilled Water System Optimizer does not support BACnet MS/TP or BACnet ARCNET networks.

Ethernet wiring specifications

For...
Ethernet
*
For details see the Open Controller Network Wiring Guide.
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
Chilled Water System Optimizer v2
Installation and Start-up Guide
Port type(s)
Ethernet
EIA-485
Rnet
Use...
CAT5e or higher Ethernet cable
Baud rate(s)
10 Mbps
100 Mbps
9600, 19.2k, or 38.4k bps
115.2 kbps
13
Wiring for communications
Use for
LAN connection
Third-party communication
Configuration
System start-up and
troubleshooting
Maximum Length
328 feet (100 meters)
CARRIER CORPORATION ©2019
All rights reserved