Carrier OPN-OPT-OL Installation And Startup Manual page 77

Chilled water system optimizer v2
Table of Contents

Advertisement

Point Name/Description
Pause & Hold is: OFF — Displays status.
Pause & Hold Criteria — Displays statuses and values.
Automatic "Quick Cool Down" - Override of the Optimizer Reset & Lower the Supply
Temperature Setpoint
1. Drop chws temperature if building gets too warm due to increasing requests for
cooling
In the Occupied Mode: Drop chws temperature if more than __ cooling requests
hysteresis __, are received
In the Unoccupied Mode: Drop chws temperature if more than __ cooling requests
hysteresis __, are received
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
Building Occupancy Status: ___ Mode — Displays status.
Total Cool Request:_.__ — Displays value.
2. OR Drop chws temperature if chilled water return temperature is > __ degrees
with a hysteresis of __
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
3. OR Drop chws temperature if chilled water return - supply temperature is < __
degrees
with a hysteresis of __
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
4. OR Drop chws temperature if building relative humidity is > __%
with a hysteresis of __
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
Current Building Relative Humidity is _.__% — Displays value.
Chilled Water System Optimizer v2
Installation and Start-up Guide
Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
73
Range
D:
3
D:
1
D:
6
D:
1
D:
1:00 (mm:ss)
R:
1:00 to 3:00 (mm:ss)
D:
58°F
R:
54 to 60°F
D:
2°F
R:
1 to 3 °F
D:
8:00 (mm:ss)
R:
1:00 to 10:00 (mm:ss)
D:
5°F
R:
5 to 8°F
D:
0.5°F
R:
0.25 to 1°F
D:
8:00 (mm:ss)
R:
1:00 to 10:00 (mm:ss)
D:
65%
R:
50 to 100%
D:
2%
R:
2 to 10%
D:
20:00 (mm:ss)
R:
10:00 to 60:00 (mm:ss)
CARRIER CORPORATION ©2019