Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page

Appendix B: The Chilled Water System Optimizer Commissioning view of
the Properties page
NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You must
enter an integer only.
CAUTION You must disable the following before commissioning:
General Conditions & Status
1
Section 1: Set Main ON Switch to DISABLED.
Chilled Water Temperature Optimizer Reset
2
Section 1: Set the CHWS Optimizer ON Switch to DISABLED.
Condenser Water Temperature Optimizer Reset
3
Section 1: Set the CWS Optimizer ON Switch to DISABLED.
At the top of the Properties page, there is a quick overview of system statuses
ENABLED/DISABLED — Optimizer
ENABLED/DISABLED — Chilled Water Supply Reset
__.__ degrees = Setpoint
__.__ degrees = Supply Temperature
__.__ degrees = Return Temperature
ENABLED/DISABLED — Condenser Water Supply Reset
__.__ degrees = Setpoint
__.__ degrees = Temperature
__.__ degrees = Outdoor Air Temperature
__.__ degrees = Outdoor Air Wet Bulb
__.__ degrees = Total Demand
__.__ degrees = Load
__.__ degrees = Efficiency
Chilled Water System Optimizer v2
Installation and Start-up Guide
58
CARRIER CORPORATION ©2019