Carrier OPN-OPT-OL Installation And Startup Manual page 68

Chilled water system optimizer v2
Table of Contents

Advertisement

Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Point Name/Description
CHILLER POWER INPUTS AND CAPACITIES
Are the Chiller Normal Capacities (below) in Tons or kW? (Default is tons.)
CHILLER 1*
1 CH1 ON (BNI2) — Displays status.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
1 CH1 kW (BAV) — Displays value.
1 CH1 kW (ANI2) — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
Is the CH1 power input above in Amps OR kW? (Default is kW.)
If Amps: The chiller voltage is ___ volts — Enter value
If Amps: Power Factor is ___ — Enter value
CH1 Nominal Capacity is: ___ tons — Enter value.
*Continue the same settings as above up to CHILLER 8
COOLING LOAD, TEMPERATURES & FLOW INPUTS
13 Cooling Load (ANI2) — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
Use Cooling Load Input (above) OR use the Temperatures & Flow (below) to
calculate the cooling load?
If using the ___ — Displays status.
Is the Load in Tons OR kW? (Default is tons.) — Enter value.
13 CHWR Temp (ANI2) — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
Chilled Water System Optimizer v2
Installation and Start-up Guide
64
Range
D:
tons
R:
tons/kW
D:
Unlocked (unchecked)
R:
Enabled (checked)
D:
Unlocked (unchecked)
R:
Enabled (checked)
D:
kW
R:
Amps/kW
D:
225
R:
Chiller capacity
D:
Unlocked (unchecked)
R:
Enabled (checked)
D:
Cooling Load Input
R:
Cooling Load Input
Temperatures & Flow
D:
tons
R:
tons/kW
D:
Unlocked (unchecked)
R:
Enabled (checked)
CARRIER CORPORATION ©2019
All rights reserved