Carrier OPN-OPT-OL Installation And Startup Manual page 76

Chilled water system optimizer v2
Table of Contents

Advertisement

Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Point Name/Description
Automatic "Pause & Hold" Override of the Optimizer Reset & Pause at its Current
Reset Setpoint
1. Pause Reset if CHWRT is >__ degrees
with hysteresis of __
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
2. OR Pause Reset if CHWRT-CHWST is <__degrees
with hysteresis of __
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
3. OR Pause Reset if Building Relative Humidity is > __%
with hysteresis of __
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
Use the __ building relative humidity from networked sensor values to determine
if it is too high.
Current Building Relative Humidity is __.__% — Displays value.
4. OR Pause Reset if Load is > __% capacity
with hysteresis of __%
__(Pause is default, Algorithm will Cool Down otherwise)
5. OR Pause Reset, for a remote condition, if the "Remote Pause" BBV receives a
binary ON signal
for __:__ (mm:ss)
Present output is False for __:__ (mm:ss). — Displays value.
Automatic Pause & Hold of Chilled Water Reset - Status
Chilled Water System Optimizer v2
Installation and Start-up Guide
72
Range
D:
46°F
R:
45 to 50°F
D:
1°F
R:
1 to 3°F
D:
4:00 (mm:ss)
R:
2:00 to 10:00 (mm:ss)
D:
6°F
R:
2 to 7°F
D:
1°F
R:
1 to 3°F
D:
4:00 (mm:ss)
R:
2:00 to 10:00 (mm:ss)
D:
60%
R:
50 to 100%
D:
2%
R:
2 to 10%
D:
20:00 (mm:ss)
R:
10:00 to 60:00 (mm:ss)
D:
Average
R:
Average/Maximum
D:
90%
R:
70 to 100%
D:
5%
R:
2 to 10%
D:
Pause
R:
Pause/Cool Down
D:
60%
R:
50 to 100%
D:
20:00 (mm:ss)
R:
10:00 to 60:00 (mm:ss)
CARRIER CORPORATION ©2019