Communications wiring
Set the remaining DIP switches as follows:
4
BACnet MS/TP DIP switch settings
8
Off
The following example shows the DIP switches set for 76.8k (Carrier default), and BACnet MS/TP.
Connect the BACnet MS/TP network to the controller's J19 Network Comm port. Connect to Net+, Net-, and
5
SHLD.
Wire specifications
A dedicated 22 AWG shielded twisted pair wire (EIA 485)
Maximum wire length 2000 feet (610 meters) or 32 nodes
Devices should be daisy-chained and not star-wired
Attach the drain/shield wire to both ends of the network segment and through every controller
NOTE Use the same polarity throughout the network segment.
Turn on the RTU Open's power.
6

Adjusting BACnet MS/TP properties using an Equipment Touch

You may need to adjust the following BACnet MS/TP protocol timing settings using the Equipment Touch.
Max Masters - defines the highest MS/TP Master MAC address on the MS/TP network.
For example, if there are 3 master nodes on an MS/TP network, and their MAC addresses are 1, 8, and 16, then
Max Masters would be set to 16 (since this is the highest MS/TP MAC address on the network).
This property optimizes MS/TP network communications by preventing token passes and "poll for master"
requests to non-existent Master nodes.
RTU Open v5
Integration Guide
7
6
5
Off
Off
Off
4
3
On
Off
6
CARRIER CORPORATION ©2019
All rights reserved