Chilled Water Temperature Optimizer Reset - Carrier OPN-OPT-OL Installation And Startup Manual

Chilled water system optimizer v2
Table of Contents

Advertisement

Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page

Chilled Water Temperature Optimizer Reset

Navigation:
i-Vu®
Point Name/Description
Optimizer Chilled Water Supply Reset Enable — Displays status.
Optimized Chilled Water Supply Setpoint AV — Displays status.
Lock the CHWS temperature setpoint output __
To __ (Final setpoint, e.g., 44 degrees F)
CAUTION Bypasses optimizer calculations.
16 CHWS STPT TEMP (REMOTE INPUT) — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
16 CHWS TEMP (REMOTE INPUT) — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
CHWR RETURN TEMP — Displays value.
Total Chiller kW/ton — Displays value.
Total Chilled Water Pump kW/ton — Displays value.
Total Airside Fan kW/ton — Displays value.
Total Chilled Water System kW/ton — Displays value.
16 Optimized CHWS Reset Heartbeat ANO Minutes — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
16 Optimized CHWS Setpoint ANO — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
Chilled Water System Optimizer v2
Installation and Start-up Guide
Properties
Control Program
>
68
Chilled Water Temperature Optimizer Reset
>
Range
R:
Disabled/Enabled
D:
Off
R:
Off/On
D:
44°F
R:
40 to 50°F
D:
Unlocked (checked)
D:
Enabled (checked)
D:
Unlocked (checked)
D:
Enabled (checked)
D:
Unlocked (unchecked)
D:
Enabled (checked)
D:
Unlocked (unchecked)
D:
Enabled (checked)
CARRIER CORPORATION ©2019