General Conditions & Status
Navigation:
i-Vu®
Point Name/Description
Optimizer Enable — Displays ENABLED or DISABLED status.
Outdoor Air Temperature— Allows this controller to use an outdoor temperature value
from another controller over the network. The remote controller must be equipped with a
network-accessible sensor value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
Outdoor Air Humidity — Allows using another controller's relative humidity value over the
network. The remote controller must be equipped with a network-accessible value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
Outdoor Air Wet Bulb Temperature — Displays the calculated value based on the OA
temperature and OA humidity values.
Total Chilled & Condenser Water System kW — Displays the current value of all the
monitored energy loads.
Total Building Cooling Load Tons — Displays the current value of all the monitored chilled
water system thermal load.
Total Chilled & Condenser Water System kW/ton — Displays the current value of all the
monitored energy loads as a function of the operating thermal load of the plant.
Chilled Water System Optimizer v2
Installation and Start-up Guide
Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Properties
Control Program
>
59
General Conditions & Status
>
Range
D:
Unlocked (checked)
D:
Enabled (checked)
D:
Unlocked (checked)
D:
Enabled (checked)
R:
0 to 5 kW/Ton
CARRIER CORPORATION ©2019
All rights reserved