Sequence
Expand Chilled Water Temperature Optimizer Reset for the following:
Section 1 - Chilled Water System Optimizer – Enable Conditions (page 69)
Verify CHWS Optimizer ON Switch is set to DISABLED.
Section 2 - Automatic Overrides of Chilled Water Reset (page 70)
Verify the following:
Automatic "Pause & Hold" override conditions have been set appropriately to match the system's operating
1
requirements.
The pause status displays: Pause & Hold is: OFF. If it is on, then determine which condition is causing it to
2
display ON and correct as necessary.
Automatic "Quick Cool Down" conditions have been set appropriately to match the system's operating
3
requirements. We suggest you utilize the default values initially unless changes are required.
The cool down status displays Quick Cool Down is: OFF. If it is on, then determine which condition is causing
4
it to display ON and correct as necessary.
Section 3 - Manual Overrides of Chilled Water Reset – and other Settings
Verify the following:
Manual "Reinitialize" & "Pause & Hold" are both Off.
1
Chilled Water System Optimizer v2
Installation and Start-up Guide
35
Start-up and Commissioning
CARRIER CORPORATION ©2019