Addressing the controller

To address the controller for third-party integration, in the i-Vu® interface, go to Driver Properties > Protocols >
Properties tab. Refer to the appropriate protocol Integration Guide for further details.
The controller needs...
An IP address

To set the controller address on the Open network

CAUTION The controller address must be unique on the IP and Open network.
If wired for power, turn off the power.
1
NOTE The controller only reads the rotary switch positions during power up or upon reset.
Use the rotary switches to set the address. Set the Tens (10's) switch to the tens digit of the address, and set
2
the Ones (1's) switch to the ones digit. Valid addresses are 1 - 99.
EXAMPLE If the controller's address is 25, point the arrow on the Tens (10's) switch to 2 and the arrow on
the Ones (1's) switch to 5.
10's
0
Turn on the controller's power.
3
CAUTION The factory default setting is 00 and must be changed to successfully install your controller.
Chilled Water System Optimizer v2
Installation and Start-up Guide
That is unique
on the...
IP Network
1's
0
Notes
Set the IP Addr DIP switch to choose one of the following:
DHCP — to obtain an IP address from a DHCP server
If there is no DHCP server, the following are the default
IP settings:
192.168.168.xx, where xx = rotary address
subnet mask = 255.255.255.0
default gateway = 192.168.168.254
Assigned — a custom IP address
NOTE The controller address is also used to
autogenerate the BACnet device instance/name for the
router. See Configuring BACnet device instance and
network number.