Installation Overview - Carrier OPN-OPT-OL Installation And Startup Manual

Chilled water system optimizer v2
Table of Contents

Advertisement

Equal-sized or unequal-sized
Up to 40 primary, secondary, and/or tertiary variable speed pumps
Up to 40 variable speed air handling unit fans serviced by chilled water system
Condenser water supply side
Up to 20 condenser water pumps
Up to 20 cooling tower variable speed or staged fans

Installation overview

WARNING This controller only supports a single Chilled Water System Optimizer program and no other
control programs.
The Chilled Water System Optimizer collects remote power (kW) values and facility thermal load values residing in
other controllers through Network Input points.
The program functions most efficiently and provides increased energy savings if all pumps and fans have variable
frequency drives and as more power inputs are measured, though it is not necessary.
Control Inputs
Power Inputs — Sum of power inputs Σ kW
Chiller power kW (required)
Chilled Water Pump kW (required)
Cooling Tower Fan kW (optional)
Condenser Water Pump kW (optional)
Air Handling Unit Fan kW (desirable but not absolutely necessary)
Load Input — Total Cooling Load
NOTE This is thermal cooling load in tons, whether calculated from the difference between chilled water
supply and return temperatures and the flow rate, or tonnage that is read directly.
Result — kW/Ton (Dividing total kW by the thermal load equals the efficiency benchmark of kW/ton)
Control Outputs – Network Outputs
The optimization program has only two control outputs. They are either Network Outputs or BACnet Analog Values.
Chilled water supply temperature reset
Condenser water supply temperature setpoint
Chilled Water System Optimizer v2
Installation and Start-up Guide
What is the Chilled Water System Optimizer?
5
CARRIER CORPORATION ©2019
All rights reserved