Optimization program is either scheduled or the Schedule present value is locked to On.
3
NOTE In order to lock the Schedule microblock from the Properties page, you must select Show Service
Config view.
Verify the outdoor air conditions are met. OAT must be greater than the configured value.
4
The part load conditions are met.
5
The current chilled water delta temperature is greater than the configured limit.
6
Verify all delays are sufficient.
7
Chilled Water System Optimizer v2
Installation and Start-up Guide
33
Start-up and Commissioning
CARRIER CORPORATION ©2019
All rights reserved