Addressing the controller
Parity
Flow Control
Click Open. A window similar to the one below appears.
7
Do one of the following:
8
To change a property value:
a. Type the number of the property, then press Enter.
b. Type the new value, then press Enter.
To take an action, type number of the action, then press Enter.
If you changed a value, type 1, then press Enter to restart the controller.
9
10 Close PuTTY.
11 Verify that you can communicate with the controller by issuing a PING command to the IP address specified in
step 12.
NOTE Your computer must be on the same subnet as the controller for the PING command to work.
12 When finished, set the controller's Router Config Mode DIP switch to OFF to restore normal functionality to
the Local Access port.
13 Cycle the controller's power to accept the Router Config Mode changes.
Chilled Water System Optimizer v2
Installation and Start-up Guide