Point Name/Description
You can use one of the following to link to the tower or pump condenser water setpoint
control.
BACnet ANO2, which writes to a remote Setpoint Analog Value
BACnet Analog value, which is read by a remote Setpoint ANI
NOTE If using a BAV, link the Optimized (Final) CWS Reset Setpoint BAV to the
remote cooling tower logic reset BACnet Analog Input. This output is a temperature
setpoint signal and when fed through the condenser water logic, should override
the current CWS temperature setpoint.
The BACnet Analog Input should go through its own safeties and ramps before
setting the CWS temperature setpoint.
The Heartbeat may be used to communicate a healthy signal to the receiving
program. Use if required or desired, but not necessary.
Optimizer Condenser Water Supply Reset Enable — Displays status.
Optimized Condenser Water Supply Setpoint AV (wetb + approach) (BAV) — Displays
value.
Lock the CWS temperature setpoint output — Locks above setpoint to a specific
value.
To __ degrees (realistic condenser water supply temperature setpoint)
NOTE Bypasses optimizer calculations - but not lower and upper limits. Use with
caution.
Outdoor Air Wet Bulb Temperature — Displays value.
Optimized Condenser Water Supply Setpoint (calculated approach) (BAV) — Displays
value.
17 CWS STPT TEMP (REMOTE INPUT) — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
17 CWS TEMP (REMOTE INPUT) — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
17 CWR TEMP (REMOTE INPUT) — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
17 CW TEMP (REMOTE INPUT) — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
Total Chiller kW/ton — Displays value.
Total Condenser Water Pump kW/ton — Displays value.
Chilled Water System Optimizer v2
Installation and Start-up Guide
Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
81
Range
R:
DISABLED / ENABLED
D:
Off
R:
Off/On
D:
0°F
R:
70 to 80°F
D:
Unlocked (unchecked)
D:
Enabled (checked)
D:
Unlocked (unchecked)
D:
Enabled (checked)
D:
Unlocked (unchecked)
D:
Enabled (checked)
D:
Unlocked (unchecked)
D:
Enabled (checked)