Section 3 - Stagger Reset - Enable Conditions - Carrier OPN-OPT-OL Installation And Startup Manual

Chilled water system optimizer v2
Table of Contents

Advertisement

Appendix A: The Chilled Water System Optimizer — Status only view of the Properties page
Point Name/Description
The following are status displays from the linked network points. See Device Address Binding (page 45).
Total Chiller kW — Displays value.
Total Chilled Water Pump kW — Displays value.
Total Condenser Water Pump kW — Displays value.
Total Cooling Tower Fan kW — Displays value.
Total Airside Fan kW — Displays value.
Total System kW (Chillers + CHWPs + CWPs + CTs + Fans) — Displays value.
Total Building Cooling Load Tons — Displays value.
Total System kW/ton — Displays value.

Section 3 - Stagger Reset - Enable Conditions

Navigation:
i-Vu®
Stagger Reset is only enabled when both Chilled Water Reset and Condenser Water Reset are running
Stagger Reset alternates between the chilled water reset and the condenser water reset calculations. When on, the program
first resets the chilled water supply temperature and calculates its impact on decreasing energy demand. It then resets the
condenser water temperature and calculates its impact on decreasing energy demand. This is a lead-lag approach.
If both chilled water and condenser water optimizer reset calculations are done simultaneously, the program would not know
whether the chilled water reset alone decreased energy demand, or the condenser water reset decreased energy demand.
Temperatures might be reset in the wrong direction.
Point Name/Description
Lead / Lag - Stagger routine for optimization is: __ — Displays On/Off status.
Condenser Water Optimization Reset is now ___ in the stagger routine. — Displays Held off or Running status.
Chilled Water Optimization Reset is now ___ in the stagger routine. — Displays Held off or Running status.
Chilled Water System Optimizer v2
Installation and Start-up Guide
Properties
Control Program
>
Stagger Reset - Enable conditions
52
General Conditions and Status
>
CARRIER CORPORATION ©2019
Section 3 -
>
All rights reserved

Advertisement

Table of Contents
loading

Table of Contents