Section 1 - Condenser Water System Optimizer - Enable Conditions - Carrier OPN-OPT-OL Installation And Startup Manual

Chilled water system optimizer v2
Table of Contents

Advertisement

Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Point Name/Description
Total Cooling Tower Fan kW/ton — Displays value.
Total Condenser Water System kW/ton — Displays value.
17 Optimized CWS Setpoint Heartbeat ANO Minutes — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.
17 Optimized CWS Setpoint ANO — Displays value.
Allows lockout if Lock at value: is checked. Allows communication if Enabled?: is
checked.

Section 1 - Condenser Water System Optimizer - Enable Conditions

Navigation:
i-Vu®
Point Name/Description
1. CWS Optimizer ON Switch:
You must set this to DISABLED until the system is setup and ready to run. This enables
the Condenser Water Supply Temperature Setpoint Reset portion of the program.
NOTE Only turn the set to ENABLED after the program is setup and ready to run. The
Main ON Switch in Section 1 - Optimizer - Primary Enable Conditions (page 60) must
also be enabled for the CWS Optimizer to be enabled.
Chilled Water System Optimizer v2
Installation and Start-up Guide
Properties
Control Program
>
Section 1 - Condenser Water System Optimizer - Enable Conditions
>
82
Range
D:
Unlocked (unchecked)
D:
Enabled (checked)
D:
Unlocked (unchecked)
D:
Enabled (checked)
Condenser Water Temperature Optimizer Reset
>
Range
D:
DISABLED
R:
DISABLED/ENABLED
CARRIER CORPORATION ©2019
All rights reserved