Reset Gain
Reset Gain and the Minimum and Maximum Reset Increments are interdependent and you might need to adjust
both more than once. The reset gain determines the reset increment and the chilled water supply temperature.
After the program has been running a while and if each increment is often at either the minimum or maximum,
then you can adjust the Reset Gain.
Each reset increment should fall between the minimum and maximum limits
The reset increment frequently increases over a response period, which is normal
If most often at the Minimum Reset Increment, then raise the reset gain
If most often at the Maximum Reset Increment, then lower the reset gain
Optional - Bias for warmer Chilled Water Supply Temperatures
After the program has been running a while, the chilled water temperature could be running cooler than expected.
This could be any one of the following reasons:
It is the best temperature for optimum energy use
The system power, flows, or tonnage inputs are turbulent and fluctuate irregularly
There is a piping or design issue
The program calculations could be misconfigured
NOTE Smoothing can help address the problem caused by turbulence or fluctuations in measurements.
If you are concerned about cooler temperatures:
Add smoothing and give a bias toward warmer supply temperatures and energy savings at the chiller(s) by
turning each Bias switch to On.
Fine tune the Bias, for lower energy savings at the chiller versus lower "system wide" energy savings.

Condenser water optimizer reset

Before starting this section, you must have already completed the sequence specified in General conditions and
status and completed the Chilled water optimizer reset.
Before commissioning the Condenser Water Temperature Optimizer Reset, verify the Chilled Water Temperature
Optimizer Reset > Section 1. Chilled Water System Optimizer - Enable Conditions (page 69) > CHWS Optimizer
ON Switch is set to DISABLED.
Chilled Water System Optimizer v2
Installation and Start-up Guide
39
Start-up and Commissioning