Addressing The Tv-Psm - Carrier TruVu ChillerVu Installation And Startup Manual

Plant controller
Table of Contents

Advertisement

Addressing the TV-PSM

Addressing the TV-PSM
Set this port's address ...
IP
Port S1
Port S2
To access the controller setup through the Service Port:
Connect an Ethernet cable from a computer to the controller as shown below.
1
Turn off the computer's Wi-Fi if it is on.
2
If your computer uses a static IP address, use the following settings:
3
Address: 169.254.1.x, where x is 2 to 7
Subnet Mask: 255.255.255.248
Default Gateway: 169.254.1.1
If it uses a DHCP address, leave the address as it is.
4
Open a web browser on the computer.
5
Navigate to http://local.access or http://169.254.1.1 to see the Service Port controller setup pages.
6
See To set up the controller through the Service Port (page 42) for general information on using the controller
setup pages.
TruVu™ ChillerVu™ Plant Controller
Installation and Start-up Guide
In this location...
Service Port
On the controller's
rotary switches
Service Port
16
See...
To set the IP address (page 18)
To set the Port S1 address and baud rate (page
20)
To set the Port S2 address and baud rate (page
20)