Update time of the I/O data

You can estimate the typical update time for an I/O cycle as follows:
RPI timer (settable from 2 to 20 ms ± 10 %) default 10 ms
+ I/O processing (typically 1.4 ms, ± 1 ms jitter due to free-running cycles)
+ EM conversion (dependent on cycle time and parameter assignment of the module)
If necessary, you must take into account other influences caused by the EIP scanner and
network components by adding them.
CM 8x IO-Link + DIQ 8x24VDC M12-L 8xM12 (6ES7148-6JJ00-0BB0) communications module
Equipment Manual, 12/2022, A5E51718265-AB