1. Installation
1.3
Setting the field bus baud rate
Setting the baud rate with the Festo field bus protocol
31.25 kBd
62.5 kBd
Fig. 1/13: Setting the baud rate for the Festo field bus
1-18
Please note
It is only necessary to set the desired baud rate with the
Festo field bus protocol.
The CPV Direct automatically recognizes the baud rate for the
PROFIBUS-DP (9.2 kBd...12 MBd) and SUCOnet K
(187.5 kBd...375 kBd) protocols.
The baud rate 187.5 kBd is always used for the ABB CS31
protocol.
With the Festo field bus protocol, DIL switch elements 7 and 8
of the 8-position DIL switch are used for setting the baud rate.
187.5 kBd
375 kBd
Festo P.BE-CP-DI01-EN en 0007a