2. Commissioning PROFIBUS-DP
Fig. 2/5: Configuration with COM PROFIBUS 3.x (example with extension with one CP
input module)
Festo P.BE-CP-DI01-EN en 0007a
The program has already automatically entered the DP
identifier for the 16 inputs and outputs of the CPV valve
terminal in this mask (line 1).
3. Enter the DP identifiers for the extensions to your CP sys-
tem in lines 2 and 3 in the column "Identifier" (summary
see Fig. 2/3).
Alternative entry of the system extension in the mask
"Order Number"
You can also enter the identifiers in a mask.
1. Mark the next unused field in the column "Order number"
and click on the button "Order No. ...".
The mask "Select by Order Number" will appear
(Fig. 2/6).
2. Mark the entry which corresponds to your system exten-
sion and confirm with "Accept".
2-13