2. Commissioning PROFIBUS-DP
Octet
Designation
2 and 3
WD_Fact_1
WD_Fact_2
4
Minimum Station Delay
Responder (min T
5 and 6
Ident_Number
7
Group_Ident
8...32
User_Prm_Data
2-30
Further octets
Explanation
Range 1...255: The response monitoring time of the
CP system is transferred with these two octets:
TWD [s] = 10 ms x WD_Fact_1 x WD_Fact_2
The minimum time the CP system must wait before
)
the reply telegram may be sent to the DP Master.
SDR
Transfer of Ident number (= 009C) of the CP system;
parametrizing telegrams to the CP system will only
be accepted if the transferred and the programmed
Ident numbers are the same.
Not supported by the CP system
Not supported by the CP system
Festo P.BE-CP-DI01-EN en 0007a