1. Installation
1
Diagnosis ON
2
Diagnosis OFF
Fig. 1/12: Setting the diagnostic mode
Festo P.BE-CP-DI01-EN en 0007a
Setting the diagnostic mode
and ABB CS31)
The following diagnosis can be activated/deactivated with
switch element 8 of the 8-position DIL switch:
–
PROFIBUS-DP Device-related diagnosis active/inactive
–
ABB CS31: load voltage monitoring active/inactive
1
2
For PROFIBUS-DP:
If the device-related diagnosis is masked out with switch el-
ement 8, no device-related diagnostic information will be sent
from the valve terminal to the master system, e.g. short cir-
cuit at the outputs or undervoltage of the valves (see chapter
3.3).
5
(only for PROFIBUS-DP
1-17