20
Device Description
3.4.2

Operating Voltage

Use SELV/PELV power source only!
The TO-PASS
(Protective Extra Low Voltage) or SELV (Safety Extra Low Voltage) power
source complying with the limited power source (LPS) requirements per DIN EN
60950-1.

Table 4: Terminal assignment for operating voltage

Figure 3: Terminal assignment for operating voltage

Connection
1,2
3, 4
38
Connect the shield connection to the DIN rail!
The shield connection of the TO-PASS
must be connected to the DIN rail. The DIN rail must have a low-impedance
ground (see section "Connections" > "Ground").
761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485
®
telecontrol module must only be powered from a PELV
Short name
Uv
GND
Shield
Designation
Operating voltage (+) DC +10 ... 30 V
Operating voltage (-) DC 0 V, Ground
Enclosure screening, connection of the PE
®
telecontrol module (shield, terminal 38)
WAGO-TO-PASS® 761
Manual
Version 1.0.0