SA 07.2
SA 16.2/SAR 07.2
AMB 01.1/AMB02.1
10.3.
Push-to-run operation or self-retaining: set
Push-to-run operation
Self-retaining
10.3.1.
Push-to-run operation or self-retaining for operation commands via push buttons
10.3.2.
Push-to-run operation or self-retaining for operation commands from Remote
SAR 16.2
Set type of seating via toggle switch [S9].
Figure 30: Signal and control board
[S9]
Toggle switch
in position
in position
The operation behaviour for operation commands (OPEN, STOP, CLOSE) can be
set separately via the push buttons on the local controls or for operation commands
from Remote.
Actuator only runs in directions OPEN or CLOSE while an operation command is
being received. The actuator stops if the operation command is cancelled.
After an operation command, the actuator continues to run in directions OPEN or
CLOSE, even if the operation command is cancelled (self-retaining). The actuator
is either stopped by the STOP command or if an end position or intermediate position
has been reached.
Push-to-run operation or self-retaining for operation commands is set in the factory
and usually remains unchanged. Subsequent modification is however possible but
by interrupting or soldering a link on the signal and control board.
Figure 31: Signal and control board
[B3]
Soldering link closed = self-retaining LOCAL
[B3]
Soldering link interrupted = push-to-run operation LOCAL
The settings for push-to-run operation or self-retaining from Remote is made via a
jumper on the wiring board.
Commissioning
= limit seating
= torque seating
controls settings
41