9 Signals (output signals)

9.1 Feedback signals from actuator

The switches can be provided as single switches (1 NC and 1 NO), as tandem
switches (2 NC and 2 NO) or as triple switches (3 NC and 3 NO). The precise
version is indicated in the terminal plan or on the order-related technical data
sheet.
Table 14: Feedback signals from actuator
Feedback signal
End position OPEN/CLOSED
reached
Intermediate position reached (op-
tion)
Torque OPEN/CLOSE reached
Motor protection tripped
Running indication (option)
Position feedback signal (option)
Manual operation active (option)
Type and designation in wiring diagram
Setting via limit switches
Switches: 1 NC and 1 NO (standard)
LSC
Limit switch, closing, clockwise rotation
Limit switch, opening, counterclockwise rota-
LSO
tion
Setting via DUO limit switches
Switches: 1 NC and 1 NO (standard)
LSA
DUO limit switch, clockwise rotation
LSB
DUO limit switch, counterclockwise rotation
Setting via torque switches
Switches: 1 NC and 1 NO (standard)
TSC
Torque switch, closing, clockwise rotation
Torque switch, opening, counterclockwise ro-
TSO
tation
F1, Th
Thermal switches
Switches: 1 NC (standard)
S5, BL
Blinker transmitter
Depending on version either with potentiometer or EWG/RWG
electronic position transmitter
R2
Potentiometer
R2/2
Potentiometer in tandem arrangement (option)
B1/B2, EWG/
3- or 4-wire system (0/4 – 20 mA)
RWG
B3/B4, EWG/
2-wire system (0 – 20 mA)
RWG
Switches