Mitsubishi Electric MELSEC-L02SCPU User Manual page 23

Cpu module, built-in i/o function
Table of Contents

Advertisement

(1) Number of points used for each function
X0 to XF and Y0 to Y7 are sorted for each function.
Function
General-purpose input
0 to 16 points (input signal)
function
General-purpose output
0 to 8 points (output signal)
function
Interrupt input function
0 to 16 points (input signal)
Pulse catch function
0 to 16 points (input signal)
0 to 2CH
• Input signal: 0 to 5 points (points/channel) (depending on
High-speed counter
settings)
*1
function
• Output Signal: 0 to 2 points (points/channel) (depending on
settings)
0 to 2 axes
• Input signal: 0 to 6 points (points/axis) (depending on
*1
settings)
Positioning function
• Output signal: 2 to 3 points (points/axis) (depending on
settings)
*1
Assignment of some signals used for the high-speed counter function and positioning function (such as A phase, B
phase, and near-point dog) are fixed. When using these functions, no signal can be assigned in place of the signals.
Available range
Number of points
Input
0 to 16 points
0 to 16 points
0 to 16 points
• When using only one
• When using only one
channel: 0 to 5 points
channel: 0 to 2 points
• When using two channels
• When using two channels
simultaneously: 0 to 10 points
simultaneously: 0 to 4 points
• When using only one axis: 0
• When using only one axis: 2
to 6 points
to 3 points
• When using two axes
• When using two axes
simultaneously: 0 to 12 points
simultaneously: 4 to 6 points
CHAPTER 1 OVERVIEW
1
Output
0 to 8 points
21