3
2-pin terminal block for motor thermistor connection
4
2-pin terminal block for relay output
5
2-pin terminal block for external power supply
6
Diagnostic LED
■
Mechanical installation
Necessary tools and instructions
•
Screwdriver and a set of suitable bits
Unpacking and checking the delivery
1. Open the option package.
2. Make sure that the package contains:
•
CMOD-02 multifunction extension module
•
a mounting screw
3. Make sure that there are no signs of damage.
Installing the module
See section
Installing option modules (page
■
Electrical installation
WARNING!
Obey the instructions in chapter Safety instructions. If you ignore them, injury or
death, or damage to the equipment can occur. If you are not a qualified electrician,
do not do electrical work.
Make sure that the drive is disconnected from the input power during
installation. If the drive is already connected to the input power, wait for
5 minutes after disconnecting the input power.
Necessary tools and instructions
•
Screwdriver and a set of suitable bits
•
Cabling tools
Terminal designations
For more detailed information on the connectors, see section
Motor thermistor connection
Marking
60
PTC IN
61
PTC IN
Relay output
Marking
62
RO PTC C
63
RO PTC B
Description
PTC connection
Ground (earth) potential
Description
Common, C
Normally open, NO
Optional I/O extension modules 169
Terminal designations (page 169)
Terminal designations (page 169)
Terminal designations (page 169)
LEDs (page 171)
69).
Technical data (page
171).