Fuses (UL recognized)

UL Recognized fuses for branch circuit protection per NEC are listed below. Check that
the operating time of the fuse is below 0.1 seconds. The operating time depends on the
fuse type, supply network impedance and the cross-sectional area, material and length of
the supply cable. The fuses must be of the "non-time delay" type. Obey local regulations.
Drive type
ACQ580-34-
U
= 400 V, IEC
N
246A-4
293A-4
363A-4
442A-4
505A-4
585A-4
650A-4
U
= 480 V, IEC
N
246A-4
293A-4
365A-4
442A-4
505A-4
585A-4
650A-4
U
= 480 V, UL (NEC)
N
240A-4
302A-4
361A-4
414A-4
477A-4
Note:
See also
Implementing thermal overload and short-circuit protection (page
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Fuses with higher current rating than the recommended ones must not be used. Fuses
with lower current rating can be used.
Fuses from other manufacturers can be used if they agree with the ratings and the
melting curve of the fuse does not exceed the melting curve of the fuse mentioned in
the table.
Input current
(A)
A
212
400
257
500
321
630
401
700
401
800
505
1000
569
1000
209
400
233
500
307
630
363
700
363
800
389
1000
441
1000
209
400
258
500
307
630
363
700
418
800
Fuse
V
Manufacturer
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
Technical data 113
Type DIN
Size
43653
2
170M5408
2
170M5410
3
170M6410
3
170M6411
3
170M6412
3
170M6414
3
170M6414
2
170M5408
2
170M5410
3
170M6410
3
170M6411
3
170M6412
3
170M6414
3
170M6414
2
170M5408
2
170M5410
3
170M6410
3
170M6411
3
170M6412
3AXD00000586715
55).