160 Optional I/O extension modules
Package: Cardboard
Isolation areas:
HDI
HDI
HDI
1
Plugged to drive SLOT2
Reinforced insulation (IEC 61800-5-1:2007)
Functional insulation (IEC 61800-5-1:2007)
Relay outputs (50...52, 53...55):
Wire size max. 1.5 mm
Minimum contact rating: 12 V / 10 mA
Maximum contact rating: 250 V AC / 30 V DC / 2 A
Maximum breaking capacity: 1500 VA
115/230 V inputs (70...78):
Wire size max. 1.5 mm
Input voltage: 115 to 230 V AC ±10%
Maximum current leakage in digital off state: 2 mA
CHDI-01
1
2
2
RO4
RO5

Advertisement