158 Optional I/O extension modules
Wiring
Connect the external control cables to the applicable module terminals. Ground the outer
shield of the cables 360 degrees under a grounding clamp on the grounding shelf of the
control cables.
Relay output connection example
24 V DC
Digital input connection example
230 V AC source
■
Start-up
Setting the parameters
1. Power up the drive.
2. If no warning is shown,
•
make sure that the value of both parameters 15.02 and 15.01 is CHDI-01.
If warning A7AB Extension I/O configuration failure is shown,
•
make sure that the value of parameter 15.02 is CHDI-01.
•
set parameter 15.01 value to CHDI-01.
You can now see the parameters of the extension module in parameter group 15 I/O
extension module.
3. Set the parameters of the extension module to applicable values.
Parameter setting example for relay output
This example shows how make relay output RO4 of the extension module indicate the
reverse direction of rotation of the motor with a one-second delay.
Parameter
15.07 RO4 source
15.08 RO4 ON delay
15.09 RO4 OFF delay
RO4C
50
RO4A
51
RO4B
52
CHDI-01
65
HDI7
HDI8
66
NEUTRAL
67
CHDI -01
Setting
Reverse
1 s
1 s