112 Technical data

Fuses (IEC)

aR fuses by Cooper Bussmann for protection against short-circuit in the input power cable
of drive are listed below.
Drive type
ACQ580-34-
U
= 400 V, IEC
N
246A-4
293A-4
365A-4
442A-4
505A-4
585A-4
650A-4
U
= 480 V, IEC
N
246A-4
293A-4
365A-4
442A-4
505A-4
585A-4
650A-4
U
= 480 V, UL (NEC)
N
240A-4
302A-4
361A-4
414A-4
477A-4
Note:
See also section
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Fuses with higher current rating than the recommended ones must not be used. Fuses
with lower current rating can be used.
Fuses from other manufacturers can be used if they agree with the ratings and the
melting curve of the fuse does not exceed the melting curve of the fuse mentioned in
the table.
Ultrarapid (aR) fuses
Input
current
A
(A)
212
400
257
500
321
630
401
700
401
800
505
1000
569
1000
209
315
233
400
307
500
363
630
363
700
389
700
441
800
209
315
258
400
307
500
363
630
418
700
Implementing thermal overload and short-circuit protection (page
Fuse
2
A
s
V
74000
690
145000
690
210000
690
300000
690
465000
690
945000
690
945000
690
42000
690
74000
690
145000
690
210000
690
300000
690
300000
690
465000
690
42000
690
74000
690
145000
690
210000
690
300000
690
Type DIN 43653
Size
170M5408
2
170M5410
2
170M6410
3
170M6411
3
170M6412
3
170M6414
3
170M6414
3
170M4410
1
170M5408
2
170M5410
2
170M6410
3
170M6411
3
170M6411
3
170M6412
3
170M4410
1
170M5408
2
170M5410
2
170M6410
3
170M6411
3
3AXD00000586715
55).