WARNING!
Do not connect the +24 V AC cable to the control board ground when the control
board is powered using an external 24 V AC supply.
NPN configuration for digital inputs (X2 & X3)
Internal and external +24 V power supply connections for NPN configuration are shown in
the figure below.
Internal +24 V power supply
NPN connection (sink)
X2 & X3
10
11
12
13
14
15
16
17
18
WARNING!
Do not connect the +24 V AC cable to the control board ground when the control
board is powered using an external 24 V AC supply.
Connection for obtaining 0...10 V from analog output 2 (AO2)
To obtain 0...10 V from analog output AO2, connect a 500 ohm resistor (or two 1 kohm
resistors in parallel) between analog output AO2 and analog common ground AGND.
Examples are shown in the figure below.
500 ohm
1 kohm
1 kohm
+24V
DGND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6
Note: DI6 is not supported in the NPN configuration.
X1
8 AO2
Analog output 2. Default output 0...20 mA.
Analog common ground. Internally connected to chassis
9 AGND
through a 2 Mohm resistor.
X1
8 AO2
Analog output 2. Default output 0...20 mA.
Analog common ground. Internally connected to chassis
9 AGND
through a 2 Mohm resistor.
External +24 V power supply
NPN connection (sink)
X2 & X3
10
11
+24 V DC
12
0 V DC
13
14
15
16
17
18
Control unit 77
+24V
DGND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6