76 Control unit
2. Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V)
minus the power taken by the option modules installed on the board.
3. In scalar control: See Menu - Primary settings - Drive - Constant frequencies or parameter
group 28 Frequency reference chain.
In vector control: See Menu - Primary setting - Drive - Constant speeds or parameter
group 22 Speed reference selection.
4. Connected with jumpers at the factory.
5. Use shielded twisted-pair cables for digital signals.
6. Ground the outer shield of the cables 360 degrees at the cabinet entry.
7.
WARNING! Connect external AC power supply (24 V AC) to control unit
connectors 40 and 41. If you connect it to connector AGND, DGND or SGND,
the power supply or the control unit can get damaged.

Switches

Switch
Description
TERM
EFB link termination. Must be set
S4
to the terminated (ON) position
when the drive (or another device)
is the first or last unit on the link.
BIAS
Switches on the biasing voltages
S5
to the bus. One (and only one)
device, preferably at the end of the
bus must have the bias on.

Additional information on I/O connections

PNP configuration for digital inputs (X2 & X3)
Internal and external +24 V power supply connections for PNP configuration are shown in
the figure below.
Internal +24 V power supply
PNP connection (source)
X2 & X3
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
Position
Bus not terminated (default)
ON
TERM
Bus terminated
ON
TERM
Bias off (default)
ON
BIAS
Bias on
ON
BIAS
External +24 V power supply
PNP connection (source)
0 V DC
+24 V DC
X2 & X3
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6

Advertisement

Table of Contents
loading

Table of Contents