78 Control unit
■
Connection examples of two-wire and three-wire sensors to analog
input (AI2)
Note: The maximum capability of the auxiliary voltage output (24 V DC [250 mA]) must not
be exceeded.
An example of a two-wire sensor/transmitter supplied by the drive auxiliary voltage output
is shown below. Set the input signal to 4...20 mA, not 0...20 mA.
-
4...20 mA
P
+
I
An example of a three-wire sensor/transmitter supplied by the drive auxiliary voltage output
is shown below.The sensor is supplied through its current output and the drive feeds the
supply voltage (+24 V DC). Thus the output signal must be 4...20 mA, not 0...20 mA.
(0)4...20 mA
OUT
P
-
I
+
■
DI5 as frequency input
For setting the parameters for the digital frequency input, see the firmware manual.
■
DI6 as PTC input
If DI6 is used as a PTC input, see firmware manual for how to set parameters accordingly.
Note: If DI6 is used as a PTC input, the wiring and the PTC sensor need to be double
isolated. Otherwise the CMOD-02 I/O extension module must be used.
T
PTC
■
AI1 and AI2 as Pt100, Pt1000, Ni1000, KTY83 and KTY84 sensor inputs
(X1)
One, two or three Pt100 sensors; one, two or three Pt1000 sensors; or one Ni1000, KTY83
or KTY84 sensor for motor temperature measurement can be connected between an analog
X1
5
AI2
Process actual value measurement or reference,
0(4)...20 mA, R
6
AGND
...
10 +24V
Auxiliary voltage output, non-isolated,
11 DGND
+24 V DC, max. 250 mA
X1
5
AI2
Process actual value measurement or reference,
0(4)...20 mA, R
6
AGND
...
10 +24V
Auxiliary voltage output, non-isolated,
+24 V DC, max. 250 mA
11 DGND
= 100 ohm
in
= 100 ohm
in
"0" > kohm
"1" < 1.5 kohm
10
I
max
18
= 5 mA