ABB ACQ580-34 Hardware Manual page 81

Drives for water
Hide thumbs Also See for ACQ580-34:
Table of Contents

Advertisement

Safe torque off (STO) inputs
IN1 and IN2 (Term. 37 and 38)
Embedded fieldbus (X5)
Control panel - drive
connection
Control panel - PC
connection
Isolation areas
24 V DC logic levels: "0" < 5 V, "1" > 13 V
R
: 2.47 kohm
in
Terminal size: 0.14...2.5 mm
Connector pitch 5 mm, wire size 2.5 mm
Physical layer: EIA-485
Cable type: Shielded twisted pair cable with twisted pair for data and a wire
or pair for signal ground, nominal impedance 100...165 ohms, for example
Belden 9842
Transmission rate: 9.6...115.2 kbit/s
Termination by switch
EIA-485, male RJ-45 connector, max. cable length 100 m (328 ft)
USB Type Mini-B, max. cable length 2 m (7 ft)
1...3
AI1
4...6
AI2
7...8
AO
10...12
24 V
GND
13...15
DI
16...18
DI
34...38
EIA/R5-485
STO
SLOT 2
I/O extension
module
Panel port
Reinforced insulation (IEC/EN 61800-5-1:2007)
Functional insulation (IEC/EN 61800-5-1:2007)
The terminals on the control board fulfill the Protective Extra Low Voltage
(PELV) requirements (EN 50178): There is reinforced insulation between the
user terminals which only accept ELV voltages and terminals that accept
higher voltages (relay outputs).
Note: There is functional insulation also between the individual relay outputs.
Note: There is reinforced insulation on the power unit.
2
2
SLOT 1
Fieldbus module
Power unit
connection
EFB
connection
40, 41
Ext. 24 V
19...21
RO1
22...24
RO2
25...27
RO3
Control unit 81