170 Optional I/O extension modules
External power supply
The external power supply is needed only if you want to connect an external back-up power
supply for the drive control unit.
Note: CMOD +24V external power supply terminals are not in use with CCU-24 control unit.
External power supply to CCU-24 is connected to terminals 40 and 41 on the control unit.
Marking
40
24 V AC/DC + in
41
24 V AC/DC - in

General cabling instructions

Obey the instructions given in chapter Guidelines for planning the electrical installation.

Wiring

Connect the external control cables to the applicable module terminals. Ground the outer
shield of the cables 360 degrees under a grounding clamp on the grounding shelf of the
control cables.
Motor thermistor connection example
1)
1)
One or 3...6 PTC thermistors connected in series.
The PTC input is reinforced/double insulated. If the motor part of the PTC sensor and wiring
are reinforced/double insulated, voltages on the PTC wiring are within SELV limits.
If the motor PTC circuit is not reinforced/double insulated (ie, it is basic insulated), it is
mandatory to use reinforced/double insulated wiring between the motor PTC and CMOD-02
PTC terminal.
Relay output connection example
RO PTC C
62
63
RO
PTC B
X4
OUT1
34
OUT2
35
SGND
36
IN1
37
IN2
38
Description
External 24 V (AC/DC) input
External 24 V (AC/DC) input
CMOD-02
CCU
PTC IN
60
PTC IN
61
CMOD-02